Has the unit been filled with 10kg/cm before leaving the factory? When installing the above protective gases, the first step is to check whether the unit has pressure, how much pressure there is, whether there are any bumps or oil stains, and make records.
It is strictly prohibited to install the unit in environments that are flammable, explosive, corrosive, dusty, and humid.
The installation level error of the 5 units shall not exceed 1.5%, and the fixation shall be reliable to prevent damage to the units and excessive noise caused by loose fixation. 4. The installation of water-cooled units should be convenient for maintenance and observation. The minimum distance from the wall should not be less than 15cm, and sufficient operating space should be left at the inlet and outlet pipe ends. Multiple units share the water system, and valves must be installed at the inlet and outlet of the unit., The installation of air-cooled units must be carried out in an open environment or outdoors. The distance between the air-cooled condenser and the wall should not be less than one-third of the longest edge of the condenser, and the air outlet should be outward. The compressor should be placed in the airflow and must be protected from rainwater when installed outdoors.